Data Links Procedures

6. Set the data link mode.

Contents
Set data link mode to
manual.
Note Be sure that the data link mode in the data link parameters in the DM
Area is set to 00 when using manually set data links.
7. Register the data link tables by making the following settings for each
node.
Contents
First data link status word
Data link nodes
Area
First data link sta-
1
tus words
Numbers of data
link words
Data link offsets
Area
First data link sta-
2
tus words
Numbers of data
link words
Data link offsets
Note Offsets are used to control where data is placed within the receive ar-
ea.
8. Start the data links.
Contents
Start the data links.
Note a) Data link Start/Stop Bit (N= unit number):
CS/CJ Series:
C200HX/HG/HE:
CVM1/CV Series:
CQM1H Series:
b) The data links will not start if there is an error in the data link
tables in the startup node.
Method
Use the SYSMAC
Data link startup node
Support Software or
only
Programming Con-
The node that is used
sole.
to start the data link is
called the startup
node. It is necessary
to decide beforehand
which node will be the
startup node.
Method
Use the Controller
All nodes within the
Link Support Soft-
network
ware or CX-Pro-
Delete from the data
grammer.
link tables all nodes
that are not in a data
link.
Method
Switch the Data link
Data link startup node
Start/Stop Bit (listed
(The Start Bit can be
below) from OFF to
turned ON in more
ON using either the
then one node to
Programming Device,
make sure the data
the user program, the
links start even when
Controller Link Sup-
the startup node is
port Software or CX-
down.)
Programmer.
Word 0 of DM30000 + 100
AR 0700 (operating level #0),
AR 0704 (operating level #1)
Word 0 of DM 2000 + 100
AR 0700
Section 2-1
Nodes
Page
73
Nodes
Page
75
Nodes
Page
100
×
N
×
N
21