Omron SYSMAC CS1W-CLK11 Operation Manual page 73

Table of Contents

Advertisement

CJ-series Controller Link Units
4-2-4
Baud Rates
Baud Rate (Pins 1 and 2)
Note
4-2-5
Terminating Resistance
Note
4. Assign node addresses consecutively beginning from 01 whenever possi-
ble to minimize Network construction time.
Set the following pins for the baud rate settings (DIP switch).
Note Always turn OFF the PC's power before setting the baud rate.
Set the same baud rate for all the nodes on the Network using DIP switch pins
1 and 2 on the front of the Unit. The baud rate is set as shown below.
The maximum transmission distance will also change according to the setting.
Pins
Pin 1
OFF
ON
OFF
ON
Note The factory default setting is shown in bold.
1. Set the same baud rate for all the nodes on the Network. Normal commu-
nication cannot be performed unless the same baud rate is set for all the
nodes.
2. The default setting is 2 Mbps, 500 m.
Turn ON the terminating resistance using the switch on the bottom of the Unit
for the Units of both ends of the Network. The terminating resistance is
required at both ends of a Network to absorb unnecessary signals and reduce
noise.
The Controller Link Unit has built-in terminating resistance, which can be con-
nected simply by turning ON the slide switch.
Bottom switch
OFF (factory default)
ON
1. Always turn OFF the PC's power before setting the terminating resistance
switch.
2. Turn ON the switch to connect terminating resistance at the nodes at both
ends of the Network and turn OFF the switch at all other nodes. Normal
communication cannot be performed in the Network unless all the nodes
are set properly.
3. The TER LED indicator will light when the terminating resistance switch is
set to ON.
ON
Pins 1, 2: Baud rate
Note: The factory default settings are shown.
Baud rate
Pin 2
OFF
2 Mbps
OFF
1 Mbps
ON
500 Kbps
ON
Do not set.
ON
Not connected.
Connected.
Section 4-2
Maximum
transmission distance
500 m
800 m
1 km
Terminating resistance
57