Controller Status Read - Omron SYSMAC CS1W-CLK11 Operation Manual

Table of Contents

Advertisement

Commands and Responses for Controller Link Units
Parameters
6-5-5

CONTROLLER STATUS READ

Command Block
146
For CS/CJ-series and CQM1H-series PCs
05
01
Command
Response
code
code
Model, version (response): The Controller Link Unit's model and version are
returned as shown below, each 20 characters in ASCII code. If fewer than 20
bytes of data are used, 20 (Hex) (i.e., spaces) will be returned for the remain-
ing bytes. In the version numbers shown below, the spaces are represented
by boxes (#).
Model
Unit for C200HX/HG/HE PCs:
Unit for CVM1/CV-series PCs:
Unit for CS-series PCs:
Unit for CJ-series PCs:
Unit for CQM1H-series PCs:
Version
PCs other than CJ-series PCs: V1.00#V1.00#########
The first version number represents the Communications Controller version
number, and the second represents the Unit version number.
CJ-series PCs: V2.00#V2.00#V2.00###
The first version number represents the data link layer Communications Con-
troller version number, the second represents the network layer Communica-
tions Controller version number, and the third represents the Unit version
number.
Wired/Optical (Response)
The connection method for the Controller Link Unit (wired or optical). The con-
figuration is as follows:
Bit
Node address (response): The Controller Link Unit's node address is
returned between 01 and 20 Hex (1 to 32).
Unit Address (response): The Unit address set for the Controller Link Unit
(10 Hex + Unit number), is returned in hexadecimal. Even when there is a Unit
number setting error, the Unit address is returned.
Network Address: The Controller Link Unit's network address, as set in the
routing table, is returned in hexadecimal. When the routing table has not been
set, the address becomes 00 Hex.
Reads the Controller Link Unit's controller status.
06
01
Command
code
20 bytes
20 bytes
Model
Version
Wired/
Optical
C200HW-CLK21########
CVM1-CLK21##########
CS1W-CLK21##########
CJ1W-CLK21##########
CQM1H-CLK21#########
– : Not used
Connection type:
0: Wired
1: Optical
Section 6-5
Network
Node
Unit
address
address
address

Advertisement

Table of Contents
loading