CJ-series Controller Link Units
4-2
CJ-series Controller Link Units
4-2-1
Overview
CLK21
RUN
ERC
INS
SD
TER
ERH M/A LNK RD
UNIT
4
No.
NODE
No.
1
x10
0
ON
x10
1
BAUD
SW1
RATE
2
TER SW
ON
BD H
BD L
SHLD
4. The default setting is OFF (not connected).
The following settings are required for a Controller Link Unit used with a CJ-
series PC.
Item
Unit number
Node address
Baud rate
Terminating resistance
UNIT
4
No.
NODE
No.
1
x10
0
x10
ON
1
BAUD
SW1
RATE
2
Unit number setting switch
Node address switches
Baud rate, pins 1 and 2
Terminating resistance switch
Unit Number
Setting range
01 to F (default is 0)
Node Address
Setting range
01 to 32 (default is 01)
Baud Rate
Pins
Baud rate
Pin 1
Pin 2
OFF
OFF
2 Mbps
OFF
ON
1 Mbps
ON
OFF
500 Kbps
ON
ON
Cannot be set.
NoteFactory default setting is in bold.
Terminating Resistance
Front switch
Terminating
resistance
OFF
Not connected
(factory default)
ON
Connected
Section 4-2
Switch
Nodes
All nodes in the Network
Nodes
All nodes in the Network
Maximum
transmission
distance
500 m
Set same
rate for all
800 m
nodes in the
1 km
Network.
Nodes
All nodes in the Network
Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.
Page
56
56
57
57
Nodes
55