Setting Data Links
76
Setting item
Area 1 Data link
CIO Area: CIO 000 to CIO 6143
start word
LR Area:
DM Area: DM 0000 to DM 32767
EM Area: Banks 00 to 12, EM 0000 to EM 32767
The same area cannot be set for both area 1 and area 2. Set dif-
ferent areas.
*: When a word between LR 000 and LR 199 is specified, the
data link area will be allocated between CIO 1000 and
CIO 1199.
Number of
Remote nodes: 0 to the number of source words
words
Local node:
The total number of words in area 1 and area 2 in each node
must not exceed 1,000.
The numbers of words in both area 1 and area 2 in each node
must not be set to 0.
Offset
Remote nodes: 0 to one less than number of source words
Local node: Cannot be set.
This setting is not required if an offset is not used.
Area 2 Data link
CIO Area: CIO 000 to CIO 6143
start word
LR Area:
DM Area: DM 0000 to DM 32767
EM Area: Banks 00 to 15, EM 0000 to EM 32767
The same area cannot be set for both area 1 and area 2. Set dif-
ferent areas.
*: When a word between LR 000 and LR 199 is specified, the
data link area will be allocated between CIO 1000 and
CIO 1199.
Number of
Remote nodes: 0 to the number of source words
words
Local node:
The total number of words in area 1 and area 2 in each node
must not exceed 1,000.
The numbers of words in both area 1 and area 2 in each node
must not be set to 0.
Remote nodes: 0 to one less than number of source words
Offset
Local node:
This setting is not required if an offset is not used.
Note a) The total number of words in data link send and receive areas
must not exceed 12,000 per node.
b) The following values must be satisfied for each node for the data
link area 1 and area 2 so that the final word in the data link does
not go beyond the last word in the PC memory area.
(Data link start word – 1) + (Total number of send/receive
words in area 1 or area 2)
Setting range
LR 00 to LR 199 (*)
Set the number of words to be received.
0 to 1,000
Set the number of words to be transmitted.
Set the offset for the data to be received.
L
R 00 to LR 199 (*)
(EM must be installed)
Set the number of words to be received.
0 to 1,000
Set the number of words to be transmitted.
Set the offset for the data to be received.
Cannot be set.
@
6143 (CIO Area)
199 (LR Area)
32767 (DM Area, EM Area)
Section 5-2