Error Log; Error Log Table - Omron SYSMAC CS1W-CLK11 Operation Manual

Table of Contents

Advertisement

Error Log

Terminating Resistance Status: IR 95
9-3
Error Log
9-3-1

Error Log Table

250
Bit status
Network parameter error
(IR 19000) is 1: ON
The error log records errors that occur in the Controller Link Unit and the time
they occur. The error log can be read or cleared by using a PC-based Pro-
gramming Devices, such as the Controller Link Support Software, the CX-Pro-
grammer, or the SYSMAC Support Software, or by using the message service
(FINS commands for the Controller Link Unit.)
Errors are recorded in an error log table in the Unit's RAM, with one record for
each error and a maximum of 39 records.
Errors of significance are also recorded in the Unit's EEPROM so that when
the power to the Unit is turned OFF or reset, a record of the error will remain.
(The error log table in EEPROM automatically reads the Unit's RAM when the
power is turned ON again.)
Item
No. of records
Data code
Length of each record
Configuration of records
Record order
Probable cause
The CPU Unit's EEPROM
data link tables or the net-
work parameters are dam-
aged.
There is an error in the net-
work parameter settings, or
node address of the local
node is larger then the
maximum address set
within the network parame-
ters.
Terminating resistance status: 0: OFF
39 max.
Binary (Times are in BCD)
10 bytes
Error code: 2 bytes (Refer to page 252)
Detail code: 2 bytes (Refer to page 252)
Time: 6 bytes (Refer to the following
page)
From the oldest record to the most
recent.
Section 9-3
Probable remedy
Refer to 8-1-3 Network
Parameters and reset the
data correctly. If the error
occurs again, replace the
CPU Unit.
Either set the EEPROM
Clear Bit in the DM param-
eter area to ON, or use the
Initialize network parame-
ters operation on the Main-
tenance Menu of the
Controller Link Support
Software to initialize the
network parameters and
then cycle the power sup-
ply.
Refer to 8-1-3 Network
Parameters and reset the
network parameters or the
node address.
1: ON
Specification