Omron SYSMAC CS1W-CLK11 Operation Manual page 189

Table of Contents

Advertisement

Response Codes
Main code
20: Read not possible
21: Write not possible
Sub-
Probable cause
code
02
The data is protected.
An attempt was made to download a
file that is being uploaded.
03
The registered table does not exist or is
incorrect.
Too many files open.
04
The corresponding search data does
not exist.
05
A non-existing program no. has been
specified.
06
A non-existing file has been specified.
07
A verification error has occurred.
01
The specified area is read-only or is
write-protected.
02
The data is protected.
An attempt was made to simulta-
neously download and upload a file.
The data link tables cannot be written
manual because the Unit is set for
automatic generation.
03
The number of files exceeds the maxi-
mum permissible.
Too many files open.
05
A non-existing program no. has been
specified.
06
A non-existent file has been specified.
07
The specified file already exists.
08
Data cannot be changed.
Remedy
Execute the instruction again after issuing
the PROGRAM AREA PROTECT CLEAR
command to the PC.
Check the file name and either interrupt ser-
vicing or wait for servicing to complete
before re-executing the command.
Set or reset the registered table.
Close open files and re-execute the com-
mand.
---
Check the program number and be sure
that it is set correctly.
Check whether the correct file name was
used.
Check whether the memory contents are
correct and replace if incorrect.
Check the contents of the file. A read error
may have occurred.
If the specified area is read-only, the write
cannot be performed. If it is write-protected,
turn off the write-protect switch and execute
the instruction again.
Execute the instruction again after issuing
the PROGRAM AREA PROTECT CLEAR
command to the PC.
Check the file name and either interrupt ser-
vicing or wait for servicing to complete
before re-executing the command.
Change the data link mode to manual.
Write the file(s) again after erasing
unneeded files, or use different disk or
Memory Card that has free space.
Close open files and re-execute the com-
mand.
Check the program number and be sure
that it is set correctly.
Check the file name and execute again.
Change the name of the file and execute
the instruction again.
---
Section 6-7
173

Advertisement

Table of Contents
loading

Table of Contents