Baud Rates; Terminating Resistance - Omron SYSMAC CS1W-CLK11 Operation Manual

Table of Contents

Advertisement

CQM1H-series Controller Link Units
Note
4-5-3

Baud Rates

4-5-4

Terminating Resistance

Item
Setting method
Setting range
Node
Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.
1. Always turn OFF the PC's power before setting the node address.
2. Do not set the same node address twice within the same Network. An error
will occur if the same address is set for two different nodes. The ERC indi-
cator on the front of the Unit will light and either communications will stop,
or the INS indicator will not light and you will be unable to participate in the
Network.
3. The send sequence for the data link areas is determined according to the
sequence of node addresses for automatically set data links.
4. Assign node addresses consecutively beginning from 01 whenever possi-
ble to minimize Network construction time.
Set the following pins for the baud rate setting (DIP switch).
Note Always turn OFF the PC's power before setting the baud rate.
Set the same baud rate for all the nodes on the Network using DIP switch pins
1 and 2 on the front of the Unit. The baud rate is set as shown below.
The maximum transmission distance will also change according to the setting.
Switch
Pin 1
OFF
ON
OFF
ON
Note The factory default setting is shown in bold.
Note Set the same baud rate for all the nodes on the Network. Normal communica-
tion cannot be performed unless the same baud rate is set for all the nodes.
Turn ON the terminating resistance using the switch on the bottom of the Unit
for the Units of both ends of the Network. The terminating resistance is
required at both ends of a Network to absorb unnecessary signals and reduce
noise.
2-digit decimal
01 to 32 (default is 01)
All nodes in the Network
ON
BAUD RATE
Baud rate
Pin 2
OFF
2 Mbps
OFF
1 Mbps
ON
500 Kbps
ON
Do not set.
Section 4-5
Specifications
SW1
Maximum
transmission distance
500 m
800 m
1 km
65