Omron SYSMAC CS1W-CLK11 Operation Manual page 289

Table of Contents

Advertisement

Memory Areas
C200HX/HG/HE PCs
SR Area
Communications Instruction Response Codes (See page 134.)
Polling Node Address, Startup Node Address: SR 238, SR 242 (See page 237)
Operating level 0
SR 238
Data Link Status: SR 239 to SR 241, SR 243 to SR 245 (See pages 103, 237)
When the first data link status word for manually set data link tables or for automatically set data links is not set
or is set to 0, the data link status of only node addresses 1 to 6 will be given in the following area.
Operating
Operating
level 0
level 1
SR 239
SR 243
Node 2
SR 240
SR 244
Node 4
SR 241
SR 245
Node 6
SR 237
Operating level 1 response code
Each response code is in 2-digit hexadecimal.
Operating level 1
SR 242
Node 1
Node 3
Node 5
Operating level 0 response code
Polling node address
Startup node address
Each node address is in 2-digit BCD.
PC status
0: Inactive (user program not running)
1: Active (user program running)
PC's CPU Unit error
0: Normal
1: Error
Communications error (data link reception)
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Offset error
0: Normal
1: Error
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Remaining receive area
0: Not remaining
1: Remaining
Appendix B
Error: Offset exceeds
number of send words.
Insufficient: Receive
area is smaller than
send area. Excess data
is truncated; other data
is received.
Remaining: Receive area
is larger than send area.
Data is received and
remaining words are
cleared.
273