For the NEBS-compliant installation of Brocade MLXe-4, Brocade MLXe--8, and Brocade MLXe-16 routers
with AC and DC systems, use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire
should have an agency-approved crimped connector (provided with the device) attached to one end, with
the other end attached to building ground. The connector must be crimped with the proper tool, allowing it
to be connected to both ground screws on the enclosure. Before crimping the ground wire into the
provided ground lug, ensure the bare copper wire has been cleaned and antioxidant is applied to the bare
wire.
For the NEBS-compliant installation of Brocade MLXe-32, routers with AC and DC systems, use a ground
wire of at least 2 American Wire Gauge (AWG). The ground wire should have an agency-approved crimped
connector (provided with the device) attached to one end, with the other end attached to building ground.
The connector must be crimped with the proper tool, allowing it to be connected to both ground screws on
the enclosure. Before crimping the ground wire into the provided ground lug, ensure the bare copper wire
has been cleaned and antioxidant is applied to the bare wire.
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is required to
be applied to the mounting hardware used to attach the ground lug.
FIGURE 88 Crimping the power supply wire in the lug
1
#4 AWG for 2400W power supply
#2 AWG for 3000W power supply.
4.
Reconnect the power lugs to the power supply unit.
5.
Connect the -48V wire to the negative terminal and the 0V wire to the positive terminal.
NOTE
DC return must be isolated from the router ground (DC-I) when making connections to the power supply.
6.
Replace the safety cover. Refer to
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations.

Removing Brocade MLX-32 router DC power supplies

Follow these steps to remove a 2400W DC power supply in a Brocade MLX-32 router:
Brocade MLX Series and Brocade NetIron XMR Installation Guide
53-1004195-02
DRAFT: BROCADE CONFIDENTIAL
2
Power lug
Figure
88.
Installing a Brocade MLX-32 router
117