Installing a NetIron XMR 32000 router

attached to building ground. The connector must be crimped with the proper tool, allowing it to be
connected to both ground screws on the enclosure. Before crimping the ground wire into the provided
ground lug, insure the bare copper wire has been cleaned and antioxidant is applied to the bare wire.
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is required to
be applied to the mounting hardware used to attach the ground lug.
FIGURE 115 Crimping the power supply wire in the lug
1
AWG power supply wire
For 1200 W power supply, #8 AWG
For 1800 W power supply, #6 AWG
5.
Connect the -48V cable to the negative terminal and the 0V cable to the positive terminal as marked on the power supply.
NOTE
DC return must be isolated from the device ground (DC-I) when connecting to the power supply.
6.
Replace the transparent plastic cover and screws.
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations

Final steps

Follow these steps to complete the installation:
"Attaching a management station"
"Activating the power source"
"Verifying proper operation"
Installing a NetIron XMR 32000 router
This section describes how to install a NetIron XMR 32000 router: