Goodrive10 Series Mini VFD
Function
Name
code
Function
P00.18
restore
parameter
P01 group Start and stop control
Function
Name
code
Start
P01.00
mode
Starting
frequency
P01.01
of direct
start
Starting
P01.02
frequency
hold time
0:No operation
1:Restore the default value
2:Clear fault records
Note:
The function code will restore to 0 after
finishing the operation of the selected
function code.
Restoring to the default value will cancel
the user password, please use this function
with caution.
0: Start-up directly:start from the starting
frequency P01.01
1:Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
Starting frequency of direct start-up means the
original frequency during the VFD starting. See
P01.02 for detailed information.
Setting range: 0.00–50.00Hz
Set a proper starting frequency to increase the
torque of the VFD during starting. During the
retention time of the starting frequency, the
output frequency of the VFD is the starting
frequency. And then, the VFD will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the VFD will stop running and keep in the
stand-by state. The starting frequency is not
limited in the lower limit frequency.
Description
Description
-31-
Function parameters
Default
Modify
◎
0
Default
Modify
◎
0
◎
0.50Hz
◎
0.0s