Fig. 18 Mounting A Cable On A Terminal Connection - Beckhoff KL2535 Documentation

Pulse width current terminals
Hide thumbs Also See for KL2535:
Table of Contents

Advertisement

Wiring HD Terminals
The High Density (HD) Terminals of the KLx8xx and ELx8xx series doesn't support steady
wiring.
Note
Ultrasonically "bonded" (ultrasonically welded) conductors
Ultrasonically "bonded" conductors
It is also possible to connect the Standard and High Density Terminals with ultrasonically
"bonded" (ultrasonically welded) conductors. In this case, please note the tables concern-
Note
ing the wire-size width [} 23] below!
Wiring
Terminals for standard wiring ELxxxx / KLxxxx and terminals for steady wiring
ESxxxx / KSxxxx
Fig. 18: Mounting a cable on a terminal connection
Up to eight connections enable the connection of solid or finely stranded cables to the Bus Terminals. The
terminals are implemented in spring force technology. Connect the cables as follows:
1. Open a spring-loaded terminal by slightly pushing with a screwdriver or a rod into the square opening
above the terminal.
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal closes automatically when the pressure is released, holding the wire securely and
permanently.
Terminal housing
Wire size width
Wire stripping length
KL2535, KL2545
ELxxxx, KLxxxx
2
0.08 ... 2,5 mm
8 ... 9 mm
Version: 2.0.0
Mounting and wiring
ESxxxx, KSxxxx
2
0.08 ... 2.5 mm
9 ... 10 mm
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kl2545

Table of Contents