ELECTRICAL CONNECTION

07
Electrical Connection
Precautions
DANGER
Before connecting cables, ensure that all switch and breaker of the inverter and the battery
pack and all the switches connected to inverter and the battery pack are set to OFF. Other-
wise, the high voltage of the product may result in electric shocks.
WARNING
The device damage caused by incorrect cable connections is not covered
under any warranty.
Only certified electricians are allowed to connect cables.
Operation personnel must wear proper PPE when connecting cables.
NOTICE
The cable colors shown in the electrical connection diagrams provided in this chapter are for
reference only. Select cables in accordance with local cable specifications (green-and-yellow
cables are only used for PE).

7.1 Overview of the Connection Area

7.1.1 Overview of the Inverter Connection Area
1
2
3 4 5
6
9
7
8
9
10
28
29
Position
Designation
PV switch
1
2
2 positive and 2 negative PV connectors, PV input A
3
2 positive and 2 negative PV connectors, PV input B
4
1 positive and 1 negative BAT power connectors
5
Battery breaker*
6
Communication port(BMS, CAN/RS485, Meter, DRM**, LAN, AUX)
7
Backup connection port
8
Grid connection port
9
Connection point for an additional grounding
10
Connection port for the WiFi module
*All breakers are switched off in transportation.
**The DRM (Demand Response Enabling Device) is only for regions with AS/NZW 4777.2
safety regulations.
The following table is about DRM interface definition.
Mode
Requirement
DRM0
Operate the disconnection device
DRM1
Do not consume power
DRM2
Do not consume at more than 50% of rate power
Do not consume at more than 75% of rate power AND Source reactive power if
DRM3
capable
Increase power consumption (subject to constraints from other active DRMs)
DRM4
Do not generate power
DRM5
Do not generate at more than 50% of rate power
DRM6
Do not generate at more than 75% of rate power AND Sink reactive power if
DRM7
capable
Increase power generation (subject to constraints from other active DRMs )
DRM8