ELECTRICAL CONNECTION

07
Electrical Connection
Precautions
DANGER
Before connecting cables, ensure that all switches and breakers of the inverter
and the battery pack and all the switches connected to inverter and the battery
pack are set to OFF. Otherwise, the high voltage of the product may result in
electric shocks.
WARNING
The device damage caused by incorrect cable connections is not covered under
any warranty.
Only certified electricians are allowed to connect cables.
Operation personnel must wear proper PPE when connecting cables.
NOTICE
The cable colors shown in the electrical connection diagrams provided in this
chapter are for reference only. Select cables in accordance with local cable speci-fications
(green-and-yellow cables are only used for PE).

7.1 Overview of the Connection Area

7.1.1 Overview of the Inverter Connection Area
34
35
Position
Designation
PV switch
1
2
1 positive and 1 negative PV connectors, PV input A
1 positive and 1 negative PV connectors, PV input B
3
Communication port(BMS, CAN/RS485, Meter/Grid-CT,
4
PV-CT, DRM*, LAN, AUX )
5
Backup connection port
6
Grid connection port
7
Connection point for an additional grounding
8
Connection port for the WiFi module
9
1 positive and 1 negative BAT power connectors
10
Battery breaker**
*The DRM (Demand Response Enabling Device) is only for regions with AS/NZW 4777.2 safety regulations.
**All breakers are switched off in transportation.
The following table is about DRM interface definition.
Mode
DRM0
DRM1
DRM2
DRM3
DRM4
DRM5
DRM6
DRM7
DRM8
Requirement
Operate the disconnection device
Do not consume power
Do not consume at more than 50% of rate power
Do not consume at more than 75% of rate power AND Source reactive
power if capable
Increase power consumption (subject to constraints from other active DRMs)
Do not generate power
Do not generate at more than 50% of rate power
Do not generate at more than 75% of rate power AND Sink reactive power if
capable
Increase power generation (subject to constraints from other active DRMs)
ELECTRICAL CONNECTION