Set the Transfer function on the Digital LCD Integral Display

On the Digita l LCD Integral Displ ay only the tran sfer function can be sele cted. The exi sting parameter or
polynomial coefficients in the transm itter will be used. The coefficients can be set or m odified only by HHT
and PC.
Navigate the Digital LCD Integral Display menu, select
Function, and the Transfer functions will be available.
Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the Transfer Function on the Display: 3 – 7 – 4 – Edit

Set the Transfer function on the Digital LCD Integral Display by HHT

The Digital LCD Integral Display Transfer function setting by Hand Held Terminal is available. Please refer to
the device manual for the right operations.

Set the Transfer function on the Digital LCD Integral Display by PC

The Digital LCD Integral Display Transfer function setting by PC is available using dedicated Software. ABB
can provide the references and the Software. Please refer to the S oftware instructions for the right
operations.

Signal simulation (fixed output current)

During the start up or for diagnostic purposes, it is useful to have the possibility to generate some reference
signal to be sent to the receiver (Controller, DCS, recorder, PLC, etc.). This is possible directly by means of
the transmitter, without disconnect its electrical connection and without a 4-20 mA generator or a pressure
generator.

Fixed output current by Digital LCD Integral Display

To set 4 mA fixed output current
Navigate the Digital LCD Integral Display menu, select
Digital LCD Integral Display Keys sequence to set 4 mA fixed output current: 7 – 2 – 1
To set 20 mA fixed output current
Navigate the Digital LCD Integral Display menu, sel ect
fixed output current. Confirm.
Digital LCD Integral Display Keys sequence to set 20 mA fixed output current: 7 – 2 – 2
To set any fixed output current
Navigate the Digital LCD Integral Display menu, select
the fixed output current values will be available. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set any fixed output current: 7 – 2 – 3

Fixed output current by CoMeter

Set of the Fixed output current by Co Meter is available with th e 695 Fi eld Indicator. Ple ase refer to the
device manual for the appropriate operations.

Fixed output current by HHT

Set of the Fixed output current by Hand Held Terminal is available. Please refer to the device manual for the
appropriate operations.

Fixed output current by PC

Set of the Fixed output current by PC is available using dedicated Software. ABB can provide the references
and the Software. Please refer to the Software instructions for the appropriate operations.
364Ax-Gx Instruction Manual
Display
>
Display Settings
Diagnostics
>
Loop Test
Diagnostics
>
Loop Test
Diagnostics
>
Loop Test
>
Display Transfer
>
Set 4 mA.
Confirm.
>
for 20 mA
Set 20 m A
>
Set Custom Value
and
30