Hardware settings

Write protect mode

Changes can be prevented to the transmitter configuration data with the write protectio n electronics dip
switch 2. If the transmitter write pr
memory. Configuration changes, such as trim and reranging cannot ta ke place. In case the Digital LCD
Integral Display is installed (no access to switch), the Write protect mode can also be set by HART command
using the HHT and the PC. Please refer to the device manual and Software instruction for the right
operation.
Position the right dip switch in ON to prevent accidental or deliberate
change of configuration data.
Position the right dip switch in OFF to change the configuration data. If
data configuration is not allowed check the Software Write lock using
the HHT or PC.

Change the failsafe direction

The transmitter alarm direction is set by repositioning the electronics dip swit ch 1. The o utput value is in
accordance with NE43 NAMUR recommendations.
Check the S oftware failsafe direction is set to Hardware before the
operation. Position the l eft dip switch in L for fail low (i.e.
current: 3.7 mA)
Check the S oftware failsafe direction is set to Hardware before the
operation. Position the left dip switch in H for fail high (i.e. output
current: 22 mA)

Software settings

Write protect mode
Changes can be prevented to the transmitter configuration data with the write protectio n electronics dip
switch 2. If the transmitter write pr
memory. Configuration changes, such as trim and reranging cannot ta ke place. In case the Digital LCD
Integral Display is installed the Write protect mode can also be set by HART command using the HHT and
the PC. Please refer to the device manual and Software instruction for the right operation.
Change the failsafe direction
The transmitter alarm direction is set selecting the Failure Mode in the transmitter software. The output value
is in accordance with NE43 NAMUR recommendations.
Navigate the Digital LCD Integral Display menu, select
the Failure Mode in use wi ll be visible. To modify sel ect
following table) with the up and down keys and confirm with OK.
As per Dip-Switch
Fail High
Fail Low
Digital LCD Integral Display Keys sequence to change the failsafe direction: 2 – 4 – 1 - Edit
otection is activated the transmitter will not accept any writes to its
otection is activated the transmitter will not accept any writes to its
Device config
Edit
to give the Failure Mode control at the Hardware setting
to set the Failure Mode in high current condition (the value can be set
by the user following the appropriate procedure of this manual)
to set the Failure Mode in low current condition (the value can be set
by the user following the appropriate procedure of this manual)
364Ax-Gx Instruction Manual
L
output
H
L
H
>
Output on alarm
then scroll the de sired Failure Mode (see the
ON
OFF
ON
OFF
>
Failure Mode