Operation

Digital LCD Integral Display

The L1 " Digital LCD Int egral Display" is conne cted to the
electronics. The in-built key-pad allows both display and
transmitter configuration.
In addition, diagn ostic information is provided. The highest
priority message will be displayed first followe d by the n ext
message in order of priority.
Here is a list of self explanatory errors and warning messages:
"Electronic Fail",
"Sensor Elec. Fail",
"Sensor Fail",
"DAC Out of Range",
"Sensor Invalid",
"PV out of Limit",
"Sensor T Out Limit",
"Electr. T Out Limit",
"Current Out Satur",
"Current Out Fixed",
"Config. Error",
"Tot. Config Error",
"Overrange",
"Consistency Check"
For additional details see the "Transmitter Diagnostics" section of this manual.

Navigate the Digital LCD Integral Display

The Digital LCD Integral Display offers you an extensive range of functions, which are grouped into menus:
to access the menu, press the button below the display indication
Display).
to select the menu or submenus press the key close to the "Select" display indication (bottom right
position on the Display)
to exit the menu or submenus press the key close to the "Exit" display indication (bottom left position on
the Display)
to come back one step in the menu or submenus press the key close to the "Back" display indication.
to scroll through the menu (up and down in the list on the display) or submenus use two keys in the
middle

Digital LCD Integral Display list of menu and submenu functions

The Digital LCD Integral Display menu has been designed to offer self-diagnostics when used by a skilled
operator.