Ip Protection; Declarations - ABB 364G Series Manual

Table of Contents

Advertisement

Electromagnetic compatibility (EMC)
Emission:
Immunity:
Radiated electromagnetic immunity level:
Conducted electromagnetic immunity
level:
Surge immunity level
Fast transient (Burst) immunity level:
Humidity
Relative humidity:
Condensing, icing:
Vibration resistance (according to IEC 60068–2–6)
Accelerations:
Shock resistance (according to IEC 60068–2–27)
Acceleration:
Duration:
Wet and dust-laden atmospheres
The transmitter is du st and sand tight and protecte d against immersion effe cts as defined by IEC 60529
(1989) to IP 67 (IP 68 on request) or by NEMA to 4X.
Fill fluid warning
Be sure that the fill fluid can mix safely with the process fluid in case of rupture of the sensor membrane.
Corrosion
A fluid/material comp atibility table is available at www.abb.com searching for "CORROSION.pdf" or from
local ABB representatives
Data of the table are based on information from manufacturers.
All data is based on a temperature of 20°C (70°F) unless noted otherwise.
Since corrosion involves many more variables than this table considers, such as trace contaminants,
aeration or temperature-concentration profile, stress corrosion cracking and pitting, the table should be used
only as a reference i n narrowing the choice of materials that merit furt her investigation. Suitability of a
particular material is b est determined by field tes t. For this p urpose, please contact the local ABB
representatives.

IP Protection

The 364 pressure tran smitter models have been certified for a degree of protection IP67 according to E N
60529 standard. This protection is provided by the pressure transmitter enclosure.
The first cha racteristic numeral indicates the prote ction of the insid e electronics against ingress of so lid
forein objects including dusts. The assigned "6" means an enclosure dust-tight (no ingress of dust).
The second characteristic numeral indicates the protection of the inside electronics against ingress of water.
The assigned "7" means an en closure water-protected against a temporary immersion
standardized conditions of pressure and time.

Declarations

The 364 pressure transmitter models declarations are attached to this manual
2MPa, 20bar, 290psi for sensor code D
6MPa, 60bar, 870psi for sensor code U
20MPa, 200bar, 2900psi for sensor code R
90MPa, 900bar, 13050psi for sensor code V
Comply with EN 61000-6-3
Comply with EN 61000-6-2
10V/m (according to IEC 1000–4–3, EN61000–4–3)
10V (according to IEC 1000–4-6, EN 61000–4–6)
2kV (according to IEC 1000-4–5 EN 61000–4–5)
2kV (according to IEC 1000–4–4 EN 61000–4–4)
up to 100%
admissible
up to 2g at frequency up to 1000Hz
50g
11ms
364Ax-Gx Instruction Manual
in wate r under
63