Set the URV by Local Keys

Set the transmitter applied pressure as for Upper
Range Value. When th e applied p ressure is
stable push the Span lo cal adjustment key (S)
located on the terminal block and release. After
this operation the reading shall move to 20 mA. If
no changes occur repeat the operation.

Set the URV by Digital LCD Integral Display

To set the URV reading of the Digital LCD Integral Display (the engineering units have to be selected):
Navigate the Digital LCD Integral Display menu, select
and the Span values may be available.
Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the Display URV : 3 – 7 – 3 - Edit
To set the Transmitter URV without reference pressure:
Navigate the Digital LCD Integral Display menu, select
Set
URV, and the URV values may be available
Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the URV wihout pressure: 2 – 1 – 2 – 3 – Edit
To set the Transmitter URV with reference pressure:
Set the transmitter applie d pressure as for Upp er Range value (100%). Navig ate the Digit al LCD Integ ral
Device Config
Display menu, select
Select
to start the autoadjust.
OK
Digital LCD Integral Display Keys sequence to set the URV wih pressure: 2 – 1 – 1 – 2 – OK

Set the URV by CoMeter

URV configuration by CoMeter is available with the 695 Field Indicator. Please refer to the device manual for
the appropriate operations.

Set the URV by HHT

URV configuration by Hand Held Terminal is available. Please refer to the device manual for the appropriate
operations.

Set the URV by PC

URV configuration by PC is available using dedicated Software. ABB c an provide t he references and the
Software. Please refer to the Software instructions for the appropriated operations.

Special functions

The transmitter has some functions to support the user in case of applications that require advance output
configuration.

Transfer functions

The 2600T Pressure Transmitter Series provides a selection of output functions, as follows:
Display
Device Config
>
>
Rerange
Rerange with pressure
364Ax-Gx Instruction Manual
>
Display settings
>
Display URV
>
Rerange
>
Rerange no pressure
>
Set URV
(100%).
(100%),
>