Faults, causes and remedies

17.1
Mechanical faults without error
messages
17.2

Error messages

Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
Faults, causes and remedies
Settings
Pump kick time interval
Basic function
Ramp time
Automatic PWM frequency
reduction
Table 32: Factory settings
WARNING
Have faults remedied by qualified personnel only! Observe safety in-
structions.
In the event of malfunctions occurring, the fault management system provides pump
performance and functionalities that can still be achieved.
A fault that has occurred is checked continuously if technically possible and, if possible,
emergency operation or control mode is restored.
Malfunction-free pump operation is resumed as soon as the cause of the malfunction
no longer exists. Example: The electronic module is again cooled down.
NOTICE
If the pump behaves incorrectly, check that the analogue and digital inputs are con-
figured correctly.
If the malfunction cannot be rectified, consult a specialist technician or the nearest
Wilo customer service or representative location.
Faults
Causes
Pump does not start or
Cable terminal loose.
stops working.
Pump does not start or
Fuse protection defect.
stops working.
Pump runs at reduced
Stop valve on the discharge
performance.
side throttled.
Air in the suction line
Pump runs at reduced
performance.
Cavitation due to insuffi-
cient suction pressure.
Pump makes noises.
Motor has bearing damage.
Pump makes noises.
Table 33: Mechanical faults
Displays an error message on the display
ƒ
The status display will be in red colour.
ƒ
Error message, error code (E...).
The pump does not pump if an error has occurred. If the pump identifies as part of
permanent monitoring that the cause of the error no longer applies, the error mes-
sage is revoked and operation resumes.
Yonos GIGA2.0
24 h
Control mode
0 s
switched off
Remedies
Check all cable connections.
Check fuses; replace faulty
fuses.
Slowly open the stop valve.
Eliminate leakage at flanges.
Vent pump. In case of visible
leakage, replace the mechan-
ical seal.
Increase the suction pressure.
Observe the minimum inlet
pressure at the suction port.
Check slide valve and filter on
the suction side and clean if
need be.
Have the pump checked by
Wilo customer service or a spe-
cialised service centre and re-
paired if necessary.
en
Yonos GIGA2.0 ... R1
24 h
Control mode
0 s
switched off