Installation Of Cif Module - Wilo Yonos GIGA2.0-I Installation And Operating Instructions Manual

Table of Contents

Advertisement

Fig. 28: Electronic module
8

Installation of CIF module

Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
Installation of CIF module
The graphic display can be turned in 90° steps. To do this, open the upper part of the
electronic module using a screwdriver.
The graphic display is fixed in position by two snap-in hooks.
1.
Carefully open the snap-in hooks with a tool (e.g. screwdriver).
2.
Turn the graphic display to the desired position.
3.
Fix the graphic display with the snap-in hooks.
4.
Fit the upper part of the module again. Observe the screw tightening torques on
the electronic module.
Component
Fig./Item screw
(nut)
Electronic module
Fig. 28, Item 1
upper part
Fig. I, Item 2
Threaded cable
Fig. 19, Item 1
gland union nut
Threaded cable
Fig. 19, Item 1
gland
Threaded cable
Fig. 19, Item 6
gland union nut
Threaded cable
Fig. 19, Item 6
gland
Power terminals and
Fig. 20, 21
control terminals
Earthing screw
Fig. 20, Item 5
CIF module
Fig. 28, Item 4
Wilo-Connectivity
Fig. 1, Item 8
Interface cover
Table 14: Tightening torques for electronic module
*Tighten when installing the cables.
**Press with screwdriver to plug and unplug the cable.
DANGER
Risk of fatal electrical shock!
Immediate risk of fatal injury if live components are touched!
• Check whether all connections are voltage-free!
CIF modules (accessories) are used for communication between pumps and building
management systems. CIF modules are attached in the electronic module (Fig. 28,
Item 4).
ƒ
For twin-head pumps, only the main pump must be equipped with a CIF module.
ƒ
For pumps in Y-pipe applications in which the electronic modules are connected to
each other through the Wilo Net, only the main pump also requires a CIF module.
NOTICE
When using CIF module Ethernet, the use of the accessory "Connection M12 RJ45
CIF-Ethernet" is recommended.
Required for easy disconnection of the data cable connection via the SPEEDCON
socket outside of the electronic module when maintenance of the pump is required.
Thread
Tightening
torque
[Nm] ±10 %
(unless other-
wise stated)
M5
4.5
M25
11
M25x1.5
8
M20x1.5
6
M20x1.5
5
Pusher
Slot 0.6x3.5
M5
4.5
PT 30x10
0.9
M3x10
0.6
en
Installa-
tion in-
formation
*
*
*
**
41