Application And Function Of The Wilo Net Interface - Wilo Yonos GIGA2.0-I Installation And Operating Instructions Manual

Table of Contents

Advertisement

12.6
Application and function of the
Wilo Net interface
Wilo Net setting
Wilo Net termination
Wilo Net address
Fig. 78: Wilo Net menu setting
Wilo Net termination
Switched off
Switched on
Fig. 79: Wilo Net termination menu
Wilo Net address
Fig. 80: Wilo Net address menu
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
Communication interfaces: Setting and function
Wilo Net is a bus system that Wilo products (participants) can use to communicate with
each other.
Application for:
ƒ
twin-head pumps consisting of two participants
Bus topology:
The bus topology consists of several pumps (participants) connected in series. The par-
ticipants are connected via a shared cable.
The bus must be terminated at both ends of the cable. This is done for the two external
pumps in the pump menu. All other subscribers should not have activated termination.
All bus subscribers must be assigned an individual address (Wilo Net ID).
This address is set in the pump menu of the respective pump.
To schedule the pumps, select the following:
Universal
Display text
1.0
Settings
1.3
External interfaces
1.3.5
Wilo Net setting
1.3.5.1
Wilo Net termination
Possible selection:
Wilo Net termination
Switched off
Switched on
After the termination has been changed, an individual Wilo Net address is assigned to
the pumps.
To assign the Wilo Net address, select the following:
Universal
Display text
1.0
Settings
1.3
External interfaces
1.3.5
Wilo Net setting
1.3.5.2
Wilo Net address
Each pump must be assigned its own address (1 ... 2).
NOTICE
The setting range for the Wilo Net address is 1 ... 126, all values in the range
22 ... 126 may not be used.
Description
The pump's terminating resistor is
switched off.
If the pump is NOT connected at the end
of the electrical bus line, "Switched off"
must be selected.
Terminating resistor of the pump is
switched on.
If the pump is connected at the end of the
electrical bus line, "Switched on" must be
selected.
en
77