Configuration Commands; Changetag Command - Pepperl+Fuchs IUH-F190-V1 Series Manual

Read / write head for identcontrol
Hide thumbs Also See for IUH-F190-V1 Series:
Table of Contents

Advertisement

IUH-F190-V1-*
Operation
If a write command is executed next, all tags in the measurement range that are not "B" tags are
selected. These tags are assigned a 'Selected' flag. The write command is executed only for
tags with no Selected flag.
When the filter is set to "B," command MF12 (Filter Activated - Mode 2) selects all "A" and "C"
tags, and the following commands address the unselected "B" tags.
Read/write head
1
Tags "A", "B", "C"
2
Filter mask inverted
3
Selected flag
4
Difference Between Command MF - Mode 1 and Command MF - Mode 2
In both cases, the subsequent commands are applied only to the "B" tags in the measurement
range.
With MF11, "B" tags are assigned a Selected flag. With MF12, "B" tags are not assigned a
Selected flag.
If a "D" tag with a Selected flag from the operation of a different read/write head enters the
measurement range, this "D" tag will execute the subsequent commands if MF11 is activated. If
MF12 is activated, this "D" tag will not execute the subsequent commands.
7.6

Configuration Commands

The response to a configuration command is a status message from the read/write head.
During the read operation, a status message and the corresponding data are received as the
response.
7.6.1

ChangeTag Command

This command tells the R/W system with which tag type to communicate.
Command: CT <ChanNo> <TagType> <CHCK> <ETX>
Response: <Status> <ChanNo> <CHCK> <ETX>
Default:
Example:
CT180 sets the tag type for IDENTControl channel 1 to IUC80
CT180 sets a generally valid tag type, which allows the read-only code to be read out for each
tag, and therefore provides information about the chip type of the tag.
1
A
80
2
B
B
A
A
A
A
B
C
C
C
C
C
3
4
B
B
D
47