A total of 3.0 amps (internal) @ 24 VDC regulated is available from the
MPS-24A Main Power Supply during standby. No more than 6 amps
@ 24 VDC can be drawn from the MPS-24A during alarm. The MPS-24B
provides 750 mA of regulated power for system modules and 2.0 amps for
indicating appliances.
Table 2: Primary Power Standby Current Requirements
76 Installation—Installing the FC-2000
All manuals and user guides at all-guides.com
Device Type
Number of
Devices
CPU
1
MPS-24A
1
MPS-24B
1
[
AVPS-24
EFB-1
[
MPM-2
[
IZM-8
[
[
IZE-A
ICM-4, CRM-4
[
ICE-4, VCE-4
[
CRE-4
[
TCM-2, TCM-4,
[
VCM-4
DCM-4
[
AIM-200
Use the standby draw from the AIM-200
Addressable Intelligent Module Technical Bulletin
Annunciator Modules (LEDs Off)
ACM-16AT,
[
ACM-32A,
AEM-16AT,
[
AEM-32A
LCD-80
[
ACM-8R
Use the Standby Total from the ACM-8R
Annunciator
Annunciator Control Module Technical Bulletin in
Control
the Fire Management Accessories Manual
Module
(FAN 445)
Use the Standby Total from the LDM Lamp
LDM Series
Annunciators
Driver Modules Technical Bulletin in the Fire
Management Accessories Manual (FAN 445)
Annunciator Modules (Additional LED current for Annunciator LEDs illuminated
during non-alarm conditions)
ACM-16,
[
ACM-32,
AEM-16AT,
AEM-32A
NIB-96
[
Continued on next page . . .
Multiply
Current
By
in Amps
X
0.031
X
0.064
X
0.062
]
X
0.009
]
X
0.011
]
X
0.006
]
X
0.047
]
X
0.004
]
X
0.007
]
X
0.001
]
X
0
]
X
0.007
]
X
0.008
in this manual
]
X
0.040
]
X
0.002
]
X
0.100
]
X
0.016
]
X
0.022
Total
Current/Device
0.031
0.064
0.062