Venting Systems; Inspections; Chimney Height / Rise And Run; Securing Chimney Components - Hearth and Home Technologies Expedition-I Manual

Single burn rate wood-fired heater
Table of Contents

Advertisement

D. Venting Systems
Chimney Connector - It is also known as flue pipe or
stove pipe. It must be 6 inches (152mm) minimum diameter
stainless steel connector pipe.
Chimney - The chimney can be new or existing, masonry
or prefabricated and must meet the following minimum
requirements as specified below.
In Canada a full length 6 inch (152mm) S635 flue liner
required as per ULC S628.
In USA a minimum 5 ft length (1.82m), 6 inch (152mm)
diameter flue liner is required as per UL 1482.
Risk of Fire!
Follow venting manufacturer's clearances
and instructions when installing venting
system.
E. Inspections
Existing chimneys should be inspected and cleaned by a
qualified professional prior to installation. The chimney must
not have cracks, loose mortar or other signs of deterioration
and blockage. Hearth & Home recommends a NFI or CSIA
certified professional or a technician, under the direction
of a certified professional, conduct a Level II inspection per
NFPA 211.
Fire Risk
Inspection of Chimney:
• Chimney must be in good condition.
• Meets minimum standard of NFPA 211
• Factory-built chimney must be 6 inch
(152mm) UL103 HT.
F. Chimney Height / Rise and Run
This product was designed for and tested on a 6 inch
(152mm) chimney, 14 to 16 feet (420-480cm) high,
(includes appliance height) measured from the base of the
appliance. The further your stack height or diameter varies
from this configuration, the greater the likelihood it may
affect performance.
Chimney height may need to be increased by 2 - 3% per
each 1000 feet above sea level. It is not recommended to
use offsets or elbows at altitudes above 4000 feet above sea
level or when there are other factors that affect flue draft.
14
WARNING
WARNING
Asphyxiation Risk.
• DO NOT CONNECT THIS Appliance
TO A CHIMNEY FLUE SERVICING
ANOTHER APPLIANCE.
• DO NOT CONNECT TO ANY AIR DISTRIBUTION
DUCT OR SYSTEM.
May allow flue gases to enter the house.
Improper installation, adjustment, alteration, service
or maintenance can cause injury or property damage.
Refer to the owner's information manual provided with
this appliance. For assistance or additional information
consult a qualified installer, service agency or your dealer.
G. Securing Chimney Components
All joints should be secured with 3 sheet metal screws or
rivets per pipe manufacturers instructions. The sections
must be attached to the insert and to each other with the
crimped (male) end pointing toward the insert (Figure 14.1).
CRIMPED
END
TOWARDS
STOVE
Figure 14.1
Fire Risk.
Follow venting manufacturer's clearances and
instructions when installing venting system.
7094-802A
WARNING
WARNING
LINER CONNECTOR
FLUE
GAS
DIRECTION
WARNING
04/21