Step 3 If the system has connected to the remote EPO switch, you need to choose
System Info > Settings > System Setting and set EPO detection to Enable.
Step 4 View the system running diagram on the MDU to check that the UPS is working in
bypass mode.
----End

5.3.3 Starting the Inverter

UPS System User List
Table 5-4 UPS system user list
Default User
admin (administrator)
operator (common user)
Starting the UPS on the LCD
Step 1 Choose Common Functions > Inv. ON.
Step 2 In the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End

5.3.4 Powering On Loads

After the inverter starts, the UPS works in normal mode. The Bypass mode alarm
disappears. Check that the UPS has transferred to normal mode by viewing the
system running status diagram.
Procedure
Step 1 After confirming that the battery strings are properly connected, turn on the
battery string input switch. If there are multiple battery strings, turn on the switch
for each battery string and then the general switch between battery strings and
the UPS. After you turn on the battery string input switch, the No battery alarm
disappears.
Step 2 Turn on the UPS output circuit breaker QF3.
Issue 03 (2022-01-19)
NO TE
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.