Ups Cable Connection Reference - Huawei UPS5000-E User Manual

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Install the battery rack and batteries. For details, see the battery installation guide
delivered with batteries.

3.2.4 UPS Cable Connection Reference

Context
● When preparing cables, keep away from the cabinet to prevent cable scraps
● After installing cables, clean the cabinet top, bottom, copper bar wiring
● Prepare terminals onsite. The length of the copper wire should be the same as
Procedure
Step 1 Route a cable into the cabinet and bind it to a nearby beam.
Step 2 Pull the cable to the copper bar to which the cable is to be connected, determine
the cable length, and mark the cable at the position where the cable is to be cut.
Step 3 Pull the marked cable out of the cabinet, cut the cable from the marked position,
strip the cable, and crimp a terminal.
Figure 3-20 Preparing a cable terminal outside the cabinet
Choose an appropriate cabling route based on the actual situation. The figure is for reference
only.
Step 4 Connect the cable with a crimped terminal to the corresponding copper bar.
Step 5 Clean foreign matter inside the cabinet.
----End
Issue 03 (2022-01-19)
WARNING
from entering the cabinet. Cable scraps may cause sparks during power-on and
cause personal injury or device damage.
positions, and other positions. Ensure that there is no dust or scraps inside and
around the cabinet.
that of the part of the terminal that covers the conductor.
NO TE
Copyright © Huawei Technologies Co., Ltd.
3 Installation
76