Huawei UPS5000-E User Manual page 208

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0060-4
Inverter
abnormal
0061-2
Inverter alarm
0061-7
Inverter alarm
0564-1
Overload timeout
0565-1
Load impact
transfer-to-
bypass
Issue 03 (2022-01-19)
Severity
Cause
Critical
● A load short-
● A short circuit
Minor
● The I2C bus is
● The E2PROM is
Minor
The bypass
waveform is not
normal.
Critical
● The load is
● Derating
● The module is
Minor
● A large-power
● The inverter
Copyright © Huawei Technologies Co., Ltd.
Solution
1. Check load cable
circuit occurs.
2. If load cable distributions
occurs inside
the module.
(This fault
seldom
occurs.)
1. Rectify the fault and check
not normal.
faulty.
2. If the alarm is generated
● If not all modules generate
● If all modules generate the
1. Check that there is no
excessive.
2. Check that the module
reduces the
rated system
power.
3. If the alarm persists,
damaged.
1. Check the load.
RCD load is
2. If the load is normal,
instantly
connected, or
the output
load short-
circuits.
bridge short-
circuits.
B Alarm List
distributions.
are normal, replace the
power module.
whether the alarm is
cleared.
again, replace the power
module.
the alarm, start the UPS,
transfer it to normal mode,
and replace the faulty
module.
alarm, open the bypass
input circuit breaker. After
the inverter relay is closed,
close the bypass input
circuit breaker 10 seconds
later.
overload.
power is not derated due
to a fan fault.
replace the power module.
replace the power module.
200