Huawei UPS5000-E User Manual page 198

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Input frequency range
Table 9-6 Battery specifications
Item
Battery voltage (lead-acid
battery)
Battery management
Charger output power
Cold start
Charging voltage (lead-
acid battery)
The UPS supports the SmartLi. For details about the parameters, see the
User Manual .
Issue 03 (2022-01-19)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Specifications
50/60 Hz ±6 Hz (adjustable with a tolerance of 0.5–6
Hz, ±2 Hz by default)
Specifications
360–528 V DC
● 12 V battery: 30–44 batteries, 40 batteries by
default; not derated when there are 36–44
batteries; power derated to 94% when there
are 34 batteries; power derated to 80% when
there are 32 or 30 batteries
● 2 V battery: 180–264 batteries, 240 batteries by
default; not derated when there are 216–264
batteries, power derated to 94% when there
are 204–214 batteries; power derated to 80%
when there are 180–202 batteries.
The number of batteries in the positive battery
string must be the same as that of batteries in
the negative battery string.
Intelligent battery management
(6250 W±200 W) x N. The maximum charge
power of a power module is 6250 W±200 W
(maximum current limiting: 10 A). N indicates the
number of power modules in a rack.
When a mains outage occurs, batteries can start
the UPS and supply power to loads.
● Equalized charge voltage:
2.3 V/cell to 2.4 V/cell, 2.35 V/cell by default
(30–42 batteries)
2.3 V/cell to 2.35 V/cell, 2.35 V/cell by default
(44 batteries)
● Float charge voltage:
2.23 V/cell to 2.3 V/cell, 2.25 V/cell by default
(30–44 batteries)
9 Technical Specifications