Huawei UPS5000-E User Manual page 134

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Battery type
Battery
capacity(Ah)
Single battery
voltage(V)
Single battery
capacity(Ah)
Batteries in a
battery string
Number of
battery
strings
Installation
time
Maintenance
period(d)
Cell float
voltage(V/
cell)
Cell equalized
volt.(V/cell)
Dis. curr. 0.1C
EOD(V/cell)
Dis. curr. 0.3C
EOD(V/cell)
Dis. curr. 0.5C
EOD(V/cell)
Dis. curr. 1.0C
EOD(V/cell)
Issue 03 (2022-01-19)
Description
Specifies the type of batteries
connected to the UPS.
Specifies the capacity of
lithium batteries connected
to the UPS (the value is
automatically obtained).
Specifies the voltage of each
battery that is connected in
series in a battery string.
Specifies the capacity of each
battery that is connected in
series in a battery string.
Specifies the number of
batteries in a battery string.
Specifies the number of
battery strings connected in
parallel.
A battery maintenance
reminder is displayed when
the maintenance time
(counted from the
installation time) comes.
Specifies the interval for
reminding users of battery
maintenance.
Specifies the battery float
charging voltage.
Specifies the battery
equalized charging voltage.
Specifies the EOD threshold
when the discharge current is
0.1C, 0.3C, 0.5C, or 1.0C
respectively.
Copyright © Huawei Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
VRLA batt.
VRLA batt.,
Lithium batt.
-
-
12 V
2, 6, 12
Depends on
5–9999
the actual
model.
Depends on
The value
the model.
range depends
on the model.
1
1–6
-
-
0
0–365
2.25
2.23–2.30
2.35
2.30–2.40
1.80
1.80–1.90
1.80
1.80–1.90
1.75
1.75–1.85
1.60
1.60–1.75
126