Huawei UPS5000-E User Manual page 126

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
BSC mode
Altitude(m)
Top outlet fan Enable this parameter if a
Air filter
maintenance
period(d)
Issue 03 (2022-01-19)
Description
● Set this parameter to
Standard BSC mode for a
dual-bus system.
● After setting this
parameter to Standard
BSC mode, you need to
set the two UPS systems
in the dual-bus system to
BSC master system and
BSC slave system
respectively in BSC
master/slave system.
(The two UPS systems
cannot be BSC master
systems or BSC slave
systems at the same time.
If you need to change the
settings in the future,
perform operations under
the guidance of
maintenance engineers.)
NOTE
Ensure that the BSC signal cable
between the BSC master and
slave systems is properly
connected and that BSC-related
hardware is properly installed.
Set this parameter based on
the altitude of the place
where the rack is used.
top outlet fan is configured.
Then the fan running status
can be checked.
Specifies the rack air filter
maintenance interval. If you
set this parameter to 0, there
is no reminder.
Copyright © Huawei Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
Non-BSC
Non-BSC,
Standard BSC
mode
≤ 1000
≤ 1000, 1000–
2000, 2000–
3000, 3000–
4000, 4000–
5000
Disable
Disable,
Enable
0
0–365
118