Huawei UPS5000-E User Manual page 117

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
IP address
Subnet mask
Gateway
MAC address
Figure 4-14 RS485 Settings
Item
Address
Baud rate
Issue 03 (2022-01-19)
NO TE
After you restart the device, IP address allocation changes back to Manual. The IP address
is set to the IP address set previously.
Description
Specifies the IP address of the
Ethernet.
NOTICE
Ensure that the UPS IP address
is unique on the network
segment. Otherwise, the LCD
may not work properly.
Specifies the subnet mask of
the Ethernet.
Specifies the Ethernet
gateway.
Defines the physical address
of network equipment and is
not configurable.
Description
This serial port address is
allocated by the user.
Select a baud rate to match
the user's network
management conditions
onsite.
Copyright © Huawei Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
192.168.0.10
1.0.0.0–
223.255.255.25
5
255.255.255.0
0.0.0.0–
255.255.255.25
5
192.168.0.1
1.0.0.0–
223.255.255.25
5
-
-
Default Value
Value Range
1
1–254
9600
9600, 19200,
115200
109