UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Shallow
discharge test
Sched.
shallow dis.
test time
Sched.
shallow dis.
test
interval(d)
Shallow dis.
test dis.
ratio(%)
Cell charge
voltage(V/
cell)
Chg. cur.
limiting coef.
(C)
Issue 03 (2022-01-19)
Description
When certain conditions are
met, the charger shuts down,
and batteries supply power
to loads. The system records
the battery discharge data as
a reference for battery
capacity and lifespan.
Specifies the time for a
scheduled shallow discharge
test.
Specifies the interval for a
scheduled shallow discharge
test.
Specifies the proportion of
the discharge capacity to the
total discharge capacity. The
value is configurable in any
mode.
Specifies the charge voltage
of lithium batteries (the
value is automatically
obtained).
Lithium battery: You can set
the charge current limit
value. The current limit
coefficient is a multiple of
the battery capacity.
Lead-acid battery: You can
set the charge current limit
value. The current limit
coefficient is a multiple of
the battery capacity.
Copyright © Huawei Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
Disable
Disable,
Enable
00:00 - 06:00
00:00–06:00,
06:00–12:00,
12:00–18:00,
18:00–24:00
60
30~90
20
10–50
-
-
0.50
0.10~1.00
0.10
0.05–0.15
127