Huawei UPS5000-E User Manual page 155

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Issue 03 (2022-01-19)
Table 5-2 System configuration parameters
Item
Rated voltage
Rated Frequency
Number of Phases LN1
Number of Phases LN2
Secondary Load
Generator Usage
Line Priority
On the main menu screen, select device configuration and press
the device configuration screen, you can set thresholds for parameters.
The following table lists the device configuration attributes and values.
Table 5-3 Device configuration attributes and values
Item
Voltage
Thresholds
Copyright © Huawei Technologies Co., Ltd.
Values
110 V/57 V; 115 V/66
V; 120 V/70 V; 208
V/120 V; 220 V/127 V;
230 V/132 V; 240 V/138
V; 227 V/160 V; 347
V/200 V; 380 V/220 V;
400 V/230 V; 415 V/240
V; 440 V/254 V; 480
V/277 V
50 Hz; 60 Hz
3 phases with N, 3
phases without N, 1
phase
3 phases with N, 3
phases without N, 1
phase
Not Used; Opening
Only; Opening And
Closing
No Generator;
Generator In Use
Line 1-Switch I; Line 2-
Switch II; No Line
Priority
Values
Volt Threshold
–30% to –5%
Min LN1
5 Operations
Description
The default value is
380 V/220 V. Set the
parameter based on
site requirements.
The default value is 50
Hz. Set the parameter
based on site
requirements.
The default value is 3
phases with N.
The default value is 3
phases with N.
The default value is
Not Used.
The default value is No
Generator. Set the
parameter based on
site requirements.
The default value is
Line 1-Switch I. Set the
parameter based on
site requirements.
. On
Description
The step increase
is ±1%. The
default settings
147