Test Run - AUMA SQEx 05.2 Operating Instructions Manual

Part-turn actuators. control unit: electronic (mwg) with actuator controls. acexc 01.2 non-intrusive
Hide thumbs Also See for SQEx 05.2:
Table of Contents

Advertisement

SQEx 05.2
SQEx 14.2/SQREx 05.2
ACExC 01.2 Non-Intrusive Profibus DP
Information
Select main menu
Set fieldbus address
10.6.

Test run

SQREx 14.2 Control unit: electronic (MWG)
DP2 slave address M0295
Default value: 126
Setting range: 0
126
Parameter DP2 slave address is only available if redundancy (option) is available.
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
(by clicking through the menu)
or press
Display indicates: DP1 slave address
4.
Select via
Up ▲ Down ▼:
▶ DP1 slave address
▶ DP2 slave address
The black triangle ▶ indicates the current selection.
5.
Ok.
Press
Display shows the set address.
6.
The bottom row of the display indicates:
Edit→ continue with step 7
Up ▲ Down ▼ → continue with step 11
7.
Press
Edit.
Display indicates: Observer (1)
8.
Select access level via
black triangle: ▶ = current setting
white triangle: ▷ = selection (not saved yet)
Information: Required access level: Specialist (4) or higher
9.
Press
Ok.
Display indicates: Password 0***
10. Enter password (→ enter password).
Display shows the set address.
11. Enter new address via
Information: The address range is displayed in round brackets on the screen.
12. Confirm selection via
The setting for the Profibus address is complete.
Only perform test run only once all settings previously described have been
performed.
and enter IDs M0098 or M0295 (direct selection)
Up ▲ Down ▼, resulting in the following significations:
Up ▲ Down ▼.
Save.
Commissioning (basic settings)
69