AUMA SQEx 05.2 Operating Instructions Manual page 96

Part-turn actuators. control unit: electronic (mwg) with actuator controls. acexc 01.2 non-intrusive
Hide thumbs Also See for SQEx 05.2:
Table of Contents

Advertisement

Technical data
Settings/programming the Profibus DP interface
Baud rate setting
Setting the fieldbus address
Configurable process representation
via GSD file
General Profibus DP interface data
Communication protocol
Network topology
Transmission medium
Profibus DP interface
Transmission rate/cable length
Device types
Number of devices
Fieldbus access
Supported Profibus DP functions
Profibus DP ident no.
Commands and signals of the Profibus DP interface
Process representation output
(command signals)
Process representation input
(feedback signals)
Process representation input
(fault signals)
Behaviour on loss of communication
96
SQEx 05.2
SQEx 14.2/SQREx 05.2
Automatic baud rate recognition
The Profibus DP address is set via the display of the device.
For an optimum adaptation to the process control system, the process representation input (feedback
signals) can be configured as desired.
Profibus DP according to IEC 61158 and IEC 61784
Line (fieldbus) structure. When using repeaters, tree structures can also be implemented. Coupling and
uncoupling of devices during operation without affecting other devices is possible.
Twisted, screened copper cable according to IEC 61158
EIA-485 (RS-485)
Baud rate (kbit/s)
9.6
93.75
187.5
500
1,500
DP master class 1, e.g. central controllers such as PLC, PC, ...
DP master class 2, e.g. programming/configuration tools
DP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors
32 devices without repeater, with repeater expandable to 126
Token-passing between masters and polling for slaves. Mono-master or multi-master systems are pos-
sible.
Cyclic data exchange, sync mode, freeze mode, fail safe mode
0x0C4F:
Standard applications with Profibus DP-V0 and DP-V1
0x0CBD:
Applications with Profibus DP-V2
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, enable local
controls, Interlock OPEN/CLOSE
End positions OPEN, CLOSED
Actual position value
Actual torque value, requires MWG in actuator
Selector switch in position LOCAL/REMOTE
Running indication (directional)
Torque switches OPEN, CLOSED
Limit switches OPEN, CLOSED
Manual operation by handwheel or via local controls
Analogue (2) and digital (4) customer inputs
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Failure of analogue customer inputs
The behaviour of the actuator is programmable:
Stop in current position
Travel to end position OPEN or CLOSED
Travel to any intermediate position
Execute last received operation command
SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP
Max. cable length
(segment length) without repeater
1,200 m
1,000 m
400 m
200 m
Possible cable length with repeater
(total network cable length):
approx. 10 km
approx. 10 km
approx. 4 km
approx. 2 km