SQEx 05.2
SQEx 14.2/SQREx 05.2
ACExC 01.2 Non-Intrusive Profibus DP
Information
SQREx 14.2 Control unit: electronic (MWG)
Connection with support terminals for line topology
When using solid cables (single or multiple strands), additional support terminals
must be used.The support terminals (terminal blocks) are mounted above the terminal
carrier.
Figure 26: Terminal assignment of support terminals: Channel 1 (1A/1B)
[XK] Terminal assignment according to wiring diagram (customer connection):
Terminals 31 and 32 if another fieldbus device follows
Terminals 31
34 if the actuator is the last fieldbus device
Figure 27: Terminal assignment of support terminals: Channel 2 (2A/2B)
[XK] Terminal assignment according to wiring diagram (customer connection):
Terminals 35 and 36 if another fieldbus device follows
Terminals 35
38 if the actuator is the last fieldbus device
Always link A connections to green wire and B connections to red wire.
Electrical connection