AUMA SQEx 05.2 Operating Instructions Manual page 66

Part-turn actuators. control unit: electronic (mwg) with actuator controls. acexc 01.2 non-intrusive
Hide thumbs Also See for SQEx 05.2:
Table of Contents

Advertisement

Commissioning (basic settings)
Select parameter
CLOSE or OPEN
User login
Change value
Information
66
SQEx 05.2
SQEx 14.2/SQREx 05.2
3.
Select parameter either:
click via the menu
via direct display: press
Display indicates: Trip torque CLOSE
4.
Up ▲ Down ▼ to select:
Use
▶ Trip torque CLOSE
▶ Trip torque OPEN
The black triangle ▶ indicates the current selection.
5.
Press Ok.
Display shows the set value.
The bottom row indicates: Edit Esc
6.
Press Edit.
Display indicates:
-
Specialist (4) → continue with step 7
-
in bottom row Up ▲ Down ▼ Esc → continue with step 11
7.
Use
Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher.
The symbols have the following meanings:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
8.
Press Ok.
Display indicates: Password 0***
9.
Enter password (→ enter password).
Display shows the set value.
The bottom row indicates: Edit Esc
10.
Press Edit.
11. Enter new value for tripping torque via
Information: The adjustable torque range is shown in round brackets.
12. Save new value via
The tripping torque is set.
13. Back to step 4 (CLOSED or OPEN): Press
The following fault signals are issued if the torque setting performed has been reached
in mid-travel:
In the display of the local controls: Status indication S0007 Fault =
Torque fault OPEN or Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
1.
either by an operation command in the opposite direction.
-
For Torque fault OPEN: Operation command in direction CLOSE
-
For Torque fault CLOSE: Operation command in direction OPEN
2.
or, in case the torque applied is lower than the preset tripping torque:
-
in selector switch position Local control (LOCAL) via push button RESET.
-
in selector switch position Remote control (REMOTE):
-
via the fieldbus, command reset., if the fieldbus is the active command
source.
-
via a digital input (I/O interface) with RESET command if a digital input
is configured for signal RESET and the I/O interface is the active
command source.
SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP
to parameter, or
and enter ID M0088.
Up ▲ Down ▼.
Save.
Esc.