Commissioning (basic settings)
10.2.

Type of seating: set

Limit
Torque
Select main menu
Select parameter
CLOSE or OPEN
64
SQEx 05.2
SQEx 14.2/SQREx 05.2
3.
If the valve end position is not reached:
Slightly turn setting screw [2] counterclockwise until valve end position
OPEN can be safely set.
Turning the setting screw [2] clockwise results in a smaller swing angle.
Turning the setting screw [2] counterclockwise results in a larger swing
angle.
4.
Turn setting screw [2] clockwise to the stop.
This completes the setting of end stop OPEN.
5.
Check O-ring of screw plug for seat and condition, replace if damaged.
6.
Fasten and tighten screw plug [1].
Having completed this procedure, the end position detection OPEN can be set
immediately.
Valve damage due to incorrect setting!
The type of seating setting (limit or torque seating) must match the selection for
the valve.
Only change the setting with prior consent of the valve manufacturer.
Customer settings M0041
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
Default value: Limit
Setting values:
Seating in end positions via limit switching.
Seating in end positions via torque switching.
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: Press
Display indicates: End position CLOSED
4.
Use
Up ▲ Down ▼ to select:
▶ End position CLOSED
▶ End position OPEN
The black triangle ▶ indicates the current selection.
SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP
to parameter, or
and enter ID M0086 or M0087