AUMA SQEx 05.2 Operating Instructions Manual page 94

Part-turn actuators. control unit: electronic (mwg) with actuator controls. acexc 01.2 non-intrusive
Hide thumbs Also See for SQEx 05.2:
Table of Contents

Advertisement

Technical data
Features and functions
Redundancy (option)
FO cable connection (option)
Local controls
Bluetooth
Communication interface
Application functions
94
SQEx 05.2
SQEx 14.2/SQREx 05.2
Requires Profibus DP-V2 (option)
Redundant line topology with universal redundancy behaviour according to AUMA redundancy I or II
Redundant line topology and redundancy behaviour according to Profibus DP-V2 specification no. 2.212
(Primary and Backup with RedCom)
Connector types: FSMA connector
FO cables
-
Multi-mode: 62.5(50)/125 µm, range approx. 2.6 km (max. 3.0 dB/km)
Topologies: Line, star and redundant loop (with single-channel Profibus DP interface)
Baud rate: up to 1.5 Mbit/s
Optical budget:
-
Multi-mode: 8.0 dB for 62.5 µm/4.0 dB for 50 µm
Wave length: 850 nm
FO coupler by Bartec required at DCS, reference addresses: AUMA or www.bartec.de
Standard:
Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN, STOP, CLOSE, RESET
-
Local STOP
The actuator can be stopped via push button STOP of local controls if the selector
switch is in position REMOTE. (Not activated when leaving the factory.)
6 indication lights:
-
End position and running indication CLOSED (yellow), torque fault CLOSE (red),
motor protection tripped (red), torque fault OPEN (red), end position and running
indication OPEN (green), Bluetooth (blue)
Graphic LC display: illuminated
Options:
Special colours for the indication lights:
-
End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN
(yellow), motor protection tripped (violet), end position OPEN (red)
Bluetooth class II chip, version 2.1: With a range up to 10 m in industrial environments, supports the
SPP Bluetooth profile (Serial Port Profile).
Required accessories:
AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
AUMA Assistant App (Commissioning and Diagnostic Tool)
Standard:
Selectable type of seating, limit or torque seating for end position OPEN and end po-
sition CLOSED
Torque by-pass: Adjustable duration (with adjustable peak torque during start-up time)
Start and end of stepping mode as well as ON and OFF times can be set individually
for directions OPEN and CLOSE, 1 to 1,800 seconds
Any 8 intermediate positions between 0 and 100 %, reaction and signal behaviour
programmable
Running indication blinking: can be set
Positioner:
-
Position setpoint via Fieldbus interface
-
Automatic adaptation of dead band (adaptive behaviour selectable)
-
Change-over between OPEN-CLOSE control and setpoint control via Fieldbus
interface
Option:
PID process controller: with adaptive positioner, via 0/4
Profibus for process setpoint and actual process value
Automatic deblocking: Up to 5 operation trials, travel time in opposite direction can be
set
SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP
20 mA analogue inputs and

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents