Status Indications According To Auma Classification - AUMA SQEx 05.2 Operating Instructions Manual

Part-turn actuators. control unit: electronic (mwg) with actuator controls. acexc 01.2 non-intrusive
Hide thumbs Also See for SQEx 05.2:
Table of Contents

Advertisement

SQEx 05.2
SQEx 14.2/SQREx 05.2
ACExC 01.2 Non-Intrusive Profibus DP
Pivot point axis
8.2.2.

Status indications according to AUMA classification

SQREx 14.2 Control unit: electronic (MWG)
Figure 63: Indication for setpoint control (positioner)
E1
Position setpoint
E2
Actual position value
The pivot points and their operation behaviour (operation profile) are shown on the
pivot point axis by means of symbols.
The symbols are only displayed if at least one of the following functions is activated:
Operation profile M0294
Timer CLOSE M0156
Timer OPEN M0206
Figure 64: Examples: on the left pivot points (intermediate positions); on the right
stepping mode
Table 26: Symbols along the pivot point axis
Symbol
Pivot point (intermediate position)
with operation profile
|
Pivot point without reaction
Stop during operation in direction
CLOSE
Stop during operation in direction
OPEN
Stop during operation in directions
OPEN and CLOSE
Pause for operation in direction CLOSE
Pause for operation in direction OPEN
Pause for operation in directions OPEN
and CLOSE
These indications are available if the parameter Diagnostic classific. M0539 is set
to AUMA.
Warnings (S0005)
If a warning has occurred, the display shows S0005:
the number of warnings occurred
a blinking question mark after approx. 3 seconds
Figure 65: Warnings
For further information, please also refer to <Corrective action>.
Indications
Stepping mode
End of stepping mode
Start of stepping mode in direction
CLOSE
Start of stepping mode in direction
OPEN
55