Signals (output signals)

9.
Signals (output signals)
9.1.

Signals via Modbus RTU

Information
9.2.

Status signals via output contacts (digital outputs)

Conditions
Characteristics
9.2.1.

Assignment of outputs

9.2.2.

Coding the outputs

60
SQEx 05.2
SQEx 14.2/SQREx 05.2
Feedback signals via Profibus DP can be configured. Configuration is possible for
both data structure and data contents.
Configuration is defined via the GSD file only.
If required, download the GSD file (General Station Description) from the Internet:
www.auma.com
For information on the feedback signals via Profibus DP and the configuration of the
parameters via fieldbus interface, refer to Manual (Device integration fieldbus) Profibus
DP.
Output contacts are only available if a parallel interface is provided in addition to the
fieldbus interface.
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
The output contacts (outputs DOUT 1
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Default values:
Signal DOUT 1 = Fault
Signal DOUT 2 = End position CLOSED
Signal DOUT 3 = End position OPEN
Signal DOUT 4 = Selector sw. REMOTE
Signal DOUT 5 = Torque fault CLOSE
Signal DOUT 6 = Torque fault OPEN
The output signals Coding DOUT 1 Coding DOUT 6 can be set either to high active
or low active.
High active = output contact closed = signal active
Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1 = Low active
Coding DOUT 2 Coding DOUT 6 = High active
SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP
6) can be assigned to various signals.