4.1.5 Output Dry Contacts

There are six sets of programmable output dry contacts (see
touch panel to set each dry contact as normally open (NO) or normally closed (NC). Each
dry contact can be assigned with a specific event. Six out of twenty-one events can be
assigned according to your applications. For the twenty-one events, please refer to the
table below. To learn how to set up, please contact your local dealer and refer to
NOTE:
Since the output dry contacts belong to the secondary circuit, the voltage of each
dry contact's connected device should not exceed 60Vdc/ 42Vac to avoid electric
P6 (Max. 0.5A/12V)
P5 (Max. 0.5A/12V)
P4 (Max. 0.5A/12V)
P3 (Max. 0.5A/12V)
P2 (Max. 0.5A/12V)
P1 (Max. 0.5A/12V)
.
DRY F_NO
COMM_F
DRY E_NO
COMM_E
DRY D_NO
10
112
6
8
2
COMM_D
4
DRY C_NO
9
11
5
7
1
3
COMM_C
DRY B_NO
COMM_B
DRY A_NO
COMM_A
UPS
O/P DRY
CONTACT
P1
P2
P3
P4
P5
P6
4-7
4
Communication Interfaces
). Please use the
+12VS
DRY 6
+12VS
DRY 5
+12VS
DRY 4
+12VS
DRY 3
+12VS
DRY 2
+12VS
DRY 1