Single Input; On-Line Mode_ Single Input_ Single Unit - Delta Modulon DPH Series User Manual

Three phase 200-600 kva
Hide thumbs Also See for Modulon DPH Series:
Table of Contents

Advertisement

The UPS runs in eight basic operation modes, which are On-Line mode, Battery mode, Bypass
mode, Manual Bypass mode, ECO mode, Frequency Conversion mode, Green mode and Energy
Recycle mode. Besides these eight operation modes, the UPS is also designed for common battery
application and hot standby redundancy. Please see the following sections for relevant information.
NOTE:
In this user manual, the meaning of Q1, Q2, Q3, Q4 and Q5 is shown as follows.
3.1

Single Input

3.1.1 On-Line Mode_ Single Input_ Single Unit

In On-Line mode, the main AC source supplies AC power via the Input Switch (Q1) to the
to the inverter. In the meantime, the rectifier provides charging power to the batteries.
After receiving the DC power, the inverter converts it into clean and stable AC power to the
connected critical loads via the Output Switch (Q4). Please refer to
Line mode, the UPS's tri-color LED illuminates green and the text 'On-Line' appears in the
upper right corner of the screen.
MAIN
Batteries
Modulon DPH Series
Code
Q1
Input Switch
Q2
Bypass Switch
Q3
Manual Bypass Switch
Q4
Output Switch
Q5
External Battery Cabinet's Breaker
Q3
Q2
Q1
Q5
Meaning
Static Switch
Rectifier
Inverter
3-2
. During On-
LOAD
Q4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dph-600k

Table of Contents