3.2.9 Battery Mode_ Dual Input_ Parallel Units

If the main AC source is abnormal, for example, when unstable voltage or a power outage
occurs, all parallel UPSs will automatically transfer from On-Line mode to Battery mode.
During the conversion process, output voltage remains the same. During Battery mode
(parallel), each UPS's tri-color LED illuminates yellow and each UPS's LCD shows the
text 'Battery' in the upper right corner. Please refer to
power through the parallel UPSs in Battery mode.
1
BYPA.
MAIN
Batteries
2
BYPA.
MAIN
Batteries
Modulon DPH Series
Q3
Static Switch
Q2
Rectifier
Q1
Q5
Q3
Static Switch
Q2
Rectifier
Q1
Q5
3-22
Inverter
Q4
Inverter
Q4
for the path of electrical
LOAD