BYPA.
MAIN
Batteries
3.2.4 Manual Bypass Mode_ Dual Input_ Single Unit
WARNING:
1. In Manual Bypass mode, make sure that all of the breakers (except the Manual
When the UPS needs maintenance, you can manually switch the UPS to Manual Bypass
mode. To let the UPS run in Manual Bypass mode, please follow the procedures below:
1
2
Tap the LCD's ON/ OFF Button (
3
Turn ON the Manual Bypass Switch (Q3).
4
Turn OFF the Bypass Switch (Q2).
5
Turn OFF the Input Switch (Q1) and Output Switch (Q4).
6
Turn OFF each external battery cabinet's breaker (Q5).
Q3
Q2
Q1
Q5
Bypass Switch (Q3)) are in the OFF position before working on the UPS's
internal circuits. This avoids electric shock.
inside the UPS and maintenance can be performed safely. However, to avoid
electric shock, please do not touch the following parts: AC Input terminal block,
Bypass Input terminal block, UPS Output terminal block, Battery Input terminal
block, grounding terminals (see
these terminal blocks and terminals) and any copper bars connected to the
Manual Bypass Switch (Q3), as they may carry high voltage.
the connected critical loads are not protected.
Static Switch
Rectifier
Inverter
) and the 'POWER OFF?' screen will pop up to
3-17
3
Operation Modes
Q4
~
for the location of
'YES'.
LOAD