4.1.4

External Switch/ Breaker Status Dry Contacts

There are four sets of external switch/ breaker status dry contacts (S1, S2, S3 and S4),
which can be used to respectively detect the status of input, bypass, output and manual
bypass switches or breakers.
NOTE:
Only trained Delta engineers can enable the function. Please contact Delta
customer service for implementation.
(Figure 4-6: External Switch/ Breaker Status Dry Contacts)
4.1.5

Output Dry Contacts

There are six sets of programmable output dry contacts. Please use the touch panel to set
each dry contact as normally open (NO) or normally closed (NC). Each dry contact can be
assigned a specific event. Six out of twenty-one events can be assigned according to your
applications. Please refer to the table below and 7.6.6 Dry Contact Setting.
NOTE:
Since the output dry contacts belong to the secondary circuit, the voltage of each
dry contact's connected device should not exceed 60Vdc/ 42Vac to avoid electric
shock or insufficient insulation.
Ultron DPS Series
38