Parallel Units Wiring - Delta Ultron HPH Series User Manual

Hide thumbs Also See for Ultron HPH Series:
Table of Contents

Advertisement

(Figure 5-9: 20/30/40kVA UPS Single Unit Dual Input Wiring Diagram)

5.5.4 Parallel Units Wiring

NOTE:
Prior to wiring, please read Chapter 5.5.1 Precautions Prior to Wiring first.
Single Input (Parallel Units)
When there is only one AC power source, parallel unit's wiring procedures are as follows.
1. Please follow steps 1~6 stated in section Single Input (Single Unit).
2. Connect the main AC source/ output/ external battery cabinet cables to the wiring terminal
block (please refer to Figures 5-8/ 5-10).
NOTE:
Regarding Figure 5-8, each figure represents that the main AC power is the TN
system and a 3-pole protective device is installed between the UPS and the main AC
power. If your main AC power is the TT system, please install a 4-pole protective
device between the UPS and the main AC power.
3. Use the provided parallel cable to connect the parallel ports on the parallel units. Please
see Figure 2-3~2-4 for parallel port location.
4. Ground the parallel UPSs.
Ultron HPH Series
39