Extron electronics IP Link Pro xi IPL EXP I/O Series User Manual page 23

Control system expansion interfaces
Table of Contents

Advertisement

Power output (IPL EXP RIO8 only)
12 VDC and 24 VDC power output ports — The IPL EXP RIO8 includes both 12 VDC
and 24 VDC output ports for use together with the digital I/O ports to provide power to
small accessories. They remain on as long as there is no overload condition.
The 12 VDC ports supply 12 VDC to devices such as an Extron ECM S10 partition
sensor.
The 24 VDC port supplies 24 VDC to devices such as the Extron OCS 100 occupancy
sensor.
Output power capacity on these ports has an aggregate limit of 19 watts, maximum, total
for all 12 VDC and 24 VDC ports. These ports are monitored continuously for total power
draw.
When the total power draw exceeds a threshold of 17 watts but is still below 19 watts,
the IPL EXP RIO8 enters the limit mode. The Limit condition is indicated within Global
Configurator, and the ports are operational. If you have configured the unit to do so, the
IPL EXP RIO8 can issue a power overcurrent notice.
If power draw exceeds a second, higher threshold (19 watts, by default), the unit enters
overcurrent mode. Power is disabled on all 12 VDC and 24 VDC ports, and the Over
condition is indicated within Global Configurator.
Once ports are disabled, the user must disconnect or fix the attached devices to correct
the problem. If the power draw is still excessive, the ports remain off.
NOTES:
The IPL EXP RIO8 provides a maximum output of 19 watts, combined, for all the
DC output ports together.
The IPL EXP RIO8 requires a PoE+ source that provides at least 48 watts (see the
power input requirement
See the Global Configurator Help File for details on the Limit and Over conditions.
See the wiring diagrams (figure 6) on the next page.
on the previous page).